CPVC Pipes & Fittings |
| DIMENSIONS AND PRESSURE RATING CHART FOR PIPES |
Nominal Pipe
Size |
Outer Diameter
in. (mm) |
SDR 11 |
SDR 13.5 |
Wall
Thickness
in. (mm) |
Working
pressure at |
Wall
Thickness
in. (mm) |
pressure at |
| 23°C |
82°C |
23°C |
82°C |
| inch |
mm |
Average |
Tolerance |
Minimum |
Tolerance |
Kg / cm2 |
Minimum |
Tolerance |
Kg / cm2 |
| 1/2 |
15 |
0.625 |
±0.003 |
0.068 |
+0.020 |
28.1 |
7.0 |
0.055 |
+0.020 |
22.5 |
5.6 |
|
|
(15.90) |
(±0.08) |
(1.73) |
(+0.51) |
|
|
(1.40) |
(+0.51) |
|
|
| 3/4 |
20 |
0.875 |
±0.003 |
0.080 |
+0.020 |
28.1 |
7.0 |
0.065 |
+0.020 |
22.5 |
5.6 |
|
|
(22.20) |
(±0.08) |
(2.03) |
(+0.51) |
|
|
(1.65) |
(+0.51) |
|
|
| 1 |
25 |
1.125 |
±0.003 |
0.102 |
+0.020 |
28.1 |
7.0 |
0.083 |
+0.020 |
22.5 |
5.6 |
|
|
(28.60) |
(± 0.08) |
(2.59) |
(+0.51) |
|
|
(2.12) |
(+0.51) |
|
|
| 1 1/4 |
32 |
1.375 |
±0.003 |
(0.125) |
+0.020 |
28.1 |
7.0 |
0.102 |
+0.020 |
22.5 |
5.6 |
|
|
(34.90) |
(±0.08) |
(3.18) |
(+0.51) |
|
|
(2.59) |
(+0.51) |
|
|
| 1 1/2 |
40 |
1.625 |
±0.004 |
(0.148) |
+0.020 |
28.1 |
7.0 |
0.120 |
+0.020 |
22.5 |
5.6 |
|
|
(41.30) |
(±0.010) |
(3.76) |
(+0.51) |
|
|
(3.06) |
(+0.51) |
|
|
| 2 |
50 |
2.125 |
±0.004 |
0.193 |
+0.023 |
28.1 |
7.0 |
0.157 |
+0.023 |
22.5 |
5.6 |
|
|
(54) |
(±0.010) |
(4.90) |
(+0.58) |
|
|
(4.00) |
(+0.58) |
|
|
|
| |
| Solvent Cement |
| We recommend to use only specially Formulated Solvent cement supplied by the company for leak free system as quality of solvent cement plays very important role and influences the joints. |
| Consumption of solvent cement: |
| Pipe Size, Inch (mm) |
1/2(15) |
3/4 (20) |
1 (25) |
1 1/4 (32) |
1 1/2 (40) |
2(50) |
| Approx. no. of joints per liter |
1200 |
750 |
500 |
450 |
325 |
225 |
|
|
 |
|
| Available Unit : 59 ml, 118 ml, 237 ml, 473 ml, 946 ml |
| |
|
|
|
|